why do we use UPF watt meter in short circuit test of the
transformer and LPF watt meter in open circuit test of the
transformer
Answer Posted / pradeepkumar
In full load test, rated current
is made to flow and hence the
fraction of magnetising current
is less compared to the watt
component.. Hence power factor
would be nearly unity.. So UPF
wattmeter is used..
But whereas in no load test,
since the machine is not loaded,
watt component of current would
be negligible as compared to
magnetising component.. Hence
the power factor would be very
low.. So LPF wattmeter is
used..!!
| Is This Answer Correct ? | 117 Yes | 12 No |
Post New Answer View All Answers
Define noise?
difference between high and low impedance BUS BAR relay??
what is the difference between rectifier and converter and commudator?
What are the commonly used schemes for the bus zone protection?
HOW TO CALCULATE THE VT SIZING?
What is meaning of out of phase (making & breaking) capacity And how to calculate
Explain what is electric traction? Explain few advantages of electric traction system?
How to test the Secure Elite 440 Multi function meter working condition.
how dia of wire and angles are calculated for overhead shielding wire to protect substation equipment from lightening strokes???
Currently what is the highest capacity (MVA) of SPPg generator available in the market?
why asa method ZPF method is more accurate than ASA method?
how does a shunt reactor maintains the bus voltage???
why we change the direction of winding in rotor ?how we make the north and south pole?
How to choose size of the cable w.r.to current carrying capacity ...
Why choke coil is connected in series with starter in tubelight??why starter is connected in parallel to tubelight??