To attain a powerfactor more than .95, how much kvr should
we use for 100 HP of current
Answer Posted / s.arul
SOLUTION:
1 HP = 735.5 watts
100 HP = 73550 watts
KVA = KW/PF
KVA = 73.55/0.95
= 77.42 KVA
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
As we use capacitor bank in 3ph ckt to improve PF, can we use capacitor in single ph domestric use, in house we have Fan,Mixer,electric cooker,iron,tube choke they also lag the system,because it is inductive load. if it is possible to improve PF of single ph system-- if yes- type of capacitor to be used,connection diagram, working in detail. if no-- list it.
We have a couple of oil tanks at our plant. One of them does not have a lightning arrester installed. My question is it necessary to install an arrestor on every tank or will this particular one be covered by the arrestor installed on the ajdacent tank, Since all the tanks are close to each other. Basically, I want to know that if these arrestors or protection works in a parituclar area of effect or influence. Thanks
How do apply electrical 'c'license......pls advice
HOW TO CALCULATE THE HEAT AND LOAD OF LT-SUBSTATION WHICH CONTAINS 2*1MVA TRANSFORMERS,LT SWITCH BOARD,MLDB,ACB,BUSBAR,ETC...?
What is a dc motor?
what is difference between isolation and ultra isolation transformer?, what is the method of testing ?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
how to setting voltage RTCC panel
What is inrush current? how can calculateit? what is the affect of it?
Can u Explain about the electronic trivector meter and the use of data converters in them?
How to address the servo drive for motor
i have flexible wire. size of conductors is 0.190 mm & no.of conductors are 48. then size of wire comes 1.37 sqmm instead of 1.5 sqmm . the what is tolerance for this size.
how make megger test for control cable like 12c x 1.5mm and what it apply voltage and test timing details.
What will be the size of copper cable (each for 3 phase and 1 neutral) from Service connection Kit-Kat to Panel Board (i.e. to main switch) for a 6 pole 3-phase AC induction motor of 200 H.P. capacity? Amp-255 A, Frequency:- 1450 rpm.
what are your career plans upon completion of the programme and the relevance of recity generation to your professional development?