HI FRIENDS IHAVE QUESTION 1.WHAT IS PARTIALSTROKE TEST?WHY
IT IS USED ON ESD ON OFF VALVES?
Answer Posted / sebastian
ESD valve or EIV(Emergency Isolation valves) are only used
(operates)for Emergency conditions only, usually theses
valves are reamins open till incase any Emergency occures
that is fire .some times it remains open till plant next
turnaround@3-4 years).so valve trim or actuator may stuck
due to some reason and valve never clos when real
Emergency, to avoid this situation , goverment athority or
insurance company guidlines are given to plant operation
section to check availablity and functionality of ESD
valves periodically, may be each 3 month, 6 month etc.
Partial stroke: Valve start to move from its open position
to close postion only @20-25% of its total traval(to avoid
process upest)and return back.there is a Function logic
built in the ESD logic with Protection timer(incase valve
limit switch not moved from open postion at set time the
logic will re set for valve its open condition and
indicate failed.(partial stroke test failed) .
if valve moved from open position (by means of limt switch
leves its contact)logic will re set and remais for open
position and indicate succes test.
if any details requred with logic contact me
sebalukose@gmail.com
Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
i hav applied for the post of engg. in iocl so please require the past test papers fro instrumentation engg please please help me and send me the papers or tell me the pattern and type of ques asked in examination......
send me model hpcl questions pleas..........my mail id mohideen.dharvesh@gmail.com
In bently nevada vibration monitoring system,what is the reason to maintain the Resistance of the probe + extension cable equal to 95 ohm? If possible explain the basic principle of measurement with detail electronic circuits.
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?
Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com
how do i tune dearator pr control valve using PID. we set the set point is 0.6kg/cm2 now i want 0.5 to 0.7kg/cm2 limits so what should i give p,i,d values. then pls explain how do set pid values for control valve tuning?
if my flow is 20000 m3/h than which range of DPT i have to use????
key phaser where is use and work
SOME OF YOUR QUESTIONS ARE NOT MAKING ANY SENSE SO TRY AND PUT IN A LITTLE BIT MORE EFFORT BEFORE YOU POST A QUESTION. WE WILL ONLY HELP THOSE WHO WE CAN SEE ARE TRYING TO HELP THEMSELVES.
What is hp & mp seperator .& what is its working principle ?
plz tell me clearly about PID.."when v have to change I value,D value,GAIN??
How to Calibrate Temperature Switch in field
give eg of how I/P is used in control loops
hii my name is sujith...i am preparing for HPVL GET 2010... so ,,,pls help me by send any previous questions or material to my site.....(Msujith_12@in.com) thank q
What is the use of control cable?