I HAVE GOT TYPICAL PROBLEM WITH THE TEMP.INDICATION.
THE PROBLEM IS THE K-TYPE T/COUPLE OUT PUT IS CONNECTED TO
A INDICATOR.THE INDICATION FLUCTUATES SOME TIMES AND SOME
TIME IT IS STABLE.
WHEN I CHECKED OUT PUT OF T/COUPLE THE MV WILL NOT VARY.
WHERE AS INDICATION FLUCTUATES.
WHEN I GIVE MV SOURCE TO T/COUPLE EXTENSIONCABLE FROM THE
FIELD IT INDICATION IS STABLE.
WHEN GIVE MV SORCE TO INDICATOR ITS INDICATION IS STABLE.
PLEASE CLARIFY.
Answer Posted / rana mujahid
I agree with all above answers but I think the most chances
are may be TC hot junction is some time going to open and
close..........need to replace TC
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
any one can send me instrumentation previous interview papers? I prepare for MNC Company Interviews? my mail id- Rakesh.Golla@dodsaldxb.ae , and another mail rakesh.gvk@gmail.com
Explain Gas Turbine startup and shutdown sequences
what deference between panel earth and systemearth
what is the usage of QDV & VOLUME BOOSTER
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?
Isometric drawings are generated during _________________ phase of a project
how many types of spped sensors n vibration sensors?their basic principle n connection?
what is the input of digital counter during the the calibration time?
please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com
How to calibrate H2s Dectector
how do we commission inergen system?
what are the different types of Protocols? & their applications.
if my flow is 20000 m3/h than which range of DPT i have to use????
Why are the uses 24vdc in industries
1)How many tpes of vibration probe and how many tpyes of vibration. 2)how we can calibrate a vibration probe with tk3 3)what is RMS value in vibration measuring application and how we calculate it.