Answer Posted / r.murugan
IF ITS PNEUMATIC CONTROL VALVE FIRST WE HAVE TO CHECK
INSTRUMENT AIR PRESSURE THEN WE HAVE TO REGULATE THE
INSTRUMENT AIR PRESSURE REGULATOR TO I/P COVERTER AND
PNEUMATIC POSITIONER
BEFORE STROKING THE VALVE WE HAVE TO CHECK VALVE AT NEUTRAL
POSITION IF NEUTRAL POSITION THEN ONLY CAN MOVE THE THE
VALVE
IF AIR TO OPEN VALVE WHEN COMMAND 4ma VALVE POSITION SHOULD
BE CLOSE (DIRECT OPERATION) LOCAL WE HAVE TO MECHANICAL
SCALE CLOSE INDICATION
THEN INCREASE THE CURRENT 4.5ma TO 5ma to check the start
of opening the control valve
then gradually can increase and decrese the current and
corrospondingly check the stroke momemnt based on command
we have to check the feedback
| Is This Answer Correct ? | 16 Yes | 7 No |
Post New Answer View All Answers
How to calibrate Field bus transmitter? procedure ?
Can I calibrate the Electromagnetic Flow Meter on line and How.
What is first echo & echo window in radar type level transmitter?
we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks
why we use 3 wire rtd direct wiring for temperature measurement instead of temperature transmitter like bearing temperature
what is the different between deflection type measurement and null type measurement in RTD?
Why we are using reverse action in displacer types level transmitters on some Vessels?
Sir, I want junior executive, Instrumentation question papaer for IOCL, Plz send to arabinda.ghosh83@gmail.com
What is the diffrence between ff tx and non ff tx
1- Explain about HPM 2- What is the FSC and explain the configuration of FSC 3- explain the complete loop of vibration, how it works (field to control room) 4- What is the use of proxymitter? 5- During job your partner effected with H2S then what you have to do. 6- what type of gland packing uses when valve glind is leaking.
how to measure oxygen which methods are using?
I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.
describe flow nozzel principle?
draw the block diagram of a level transmitter ?
can anyone tell me about the basic concepts to consider before to start a PLC panel wiring