one KVAR takes how much amps, and how to add power capacitors
to electrical panels, for example if one of the MCC drawn
800amps means how much KVAR required
Answer Posted / wareagle
Before you can answer this question you must knoiw the load
power factor.
KVAR amps = KVAR/(kv x 1.73) eg 600 kvar 400 volts
600/
(0.4 x 1.73 = 867 amps
To determine tha KVAR required you must know the existing PF
Then you determine what you want the new PF to be before
you can calculate the new PF.
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
How to do cable sizing calculation for 750 A Neutral Earthing resistor for 33kv. the 33kv cable going to swbd. is 630mm2 3 runs.
hi, i have 3x200KVA and 2 x 80KVA UPS with battery bank of 150AH 68Nos. and 100AH 204Nos., i need to install AC either ductable or PAC type, so can you help me to calculate heat load and capacity of the AC to install.
If Dg set load increase 25%, How much increase fuel Consumption (15 kva 2 cylinder DG set)
Whether 3 phase induction motorwith 100 hp capacity , Amp 160 for which sensitive earth fault relay , type CTUM 15 can be used?
what are the components in electrical control panel (for example: 415V, 3-ph, panel to operate utility and 3-ph DG set).
Merits & Demarits of Oil circuit & Air circuit breakers ?
what is the reqirred voltage in HT motor to get full RPM on no load test?
What is ferro-resonance in electrical system? Why it occurs and what are measures to prevent it?
WE HAVE THE DC RECTIFIER 1500A, INPUT VOLTAGE IS 3 PHASE. HOW TO CALICULATE THE LOAD? 3 PHASE SIDE EITHER dC SIDE. PLEASE SUGGEST ME
WHAT IS LOAD CELL
how to ctrl motor by use of ac or dc drive.plz explain evdintly
what is the IEC standard for Power Cable installation in onshore (like in direct buried ground or above groung)
How many VSC based HVDC are there in India and the world
In our plant we have installed new MCC with ELR and CBCT which is detecting some leakage current in the system but it leading to some confusion when to check that in which feeder which is drawing current we put off the whole panel itself but still CBCT detecting some leakage current so can anybody ans me , where i am going wrong or how to detect whether its actual leakage or CBCT malfunctioning.
What is the difference between PS & metering CT (5p20,0.5 etc.)? Why in PS class CT only Vk is given ? Is PS class CT is more accurate than metering CT?