If the maximum demand is 120 KVA in a building, then what is
the Current taken according to load given ? Formula for it ?
Answer Posted / jose
120 kva means you have to supply 3 phase load.
3 phase load with 415 v and unity pf can take a current
according to eqn kva=1.732*Kv*I
I=120*1000/(415*1)=290 A appr
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
what mean by analog ,digital,numerical meters and relays? say the example?
Explain the terms real power, apparent power and reactive power for ac circuits and also the units used.
Why is a plain induction motor unsuitable for wide speed control?
what happen if the load connected to the induction motor is taken away? the same question for synchoronous generator in synch i think that the the exitation voltage will appear on the terminal only if so plz answer me
What is Phase margin?
what is the meaning of the symbol << >> put in transformer drawing
high voltage transformer input voltage,current and amps rating..distributed transformer input voltage,current and amps rating...
What is the Surge for 1.1 Phase Induction Motor(For Eg.1Hp) 2.3 Phase Induction Motor(For Eg.1Hp) 3.AirConditioner(For Eg 1Ton) 4.Refrigerator(For Eg 180Ltr or 160kW) 5.Induction Cooker 4. Ceiling Fan
What is a single phase autotransformer?
how to determine motor size for a fan application?
if the number of poles generated in stator and rotor side of an induction motor are different then what will happen and why?
Which type of motor is used in trains, what is the rating of supply used explain working principal?
Can I use star delta connected induction motor for dual supply voltage?
can indirect loading be called as phantom loading?
Thermal withstand capability under full short circuit conditions, in terms of number of times of occurrence of short circuit and corresponding anticipated percentage reduction in transformer life.