what is Dry Leg calibration and where is it used
Answer Posted / omak
Dry leg calibration is nothing but the calibration of a DP tx in an closed tank.In a closed tank , the LP side is connected with the top of the tank and HP side is connected with the bottom of the tank to measure the height of the liquid column present in the tank.
Phigh = Pgas + S.H
Plow = Pgas
DP = Phigh - Plow = S>H
Is This Answer Correct ? | 17 Yes | 4 No |
Post New Answer View All Answers
How to do gas analysers calibration in AUTO and Manually by using zero and span gas?
How to Calibrate Ultrasonic Level Transmitter in field
how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?
Do you have reference list?
There are two chlorination tonners both are connected to two pressure swithes and the pressure switch is connected to SOV which operates the valve to changeover the tonner selection i.e if pressure one tonner goes low the other tonner should come in line if it is inautomatic selection design a circuit using relays ?
What happen if we install my pressure transmitter below the elevation of pipe in natural gas service?
What is the procedure of calibration of Load cell?
How does a single acting, spring return ball valve actually work? Does it require continuous air supply?
How can i copy program (parameter) from mm440 (V.F.D.) by using BOP?
If relative y axis vibration sensor is by passed, and relative x axis and absolute sensor is left working. how much monitoring i would have risked?
what is output of FOUNDATION FIELD BUS transmitter
how many types of preheaters are in cement industry & what r they can any body explain?
Explain the key components of control loop?
line up procedure for dp type flow transmitter?
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.