Why electrical engineer use Cu Strip for transformer
neutral why not GI Strip? What if we use GI instead of Cu
does it affects the transformer performance.
Answer Posted / sam
no issue in using GI strip for transformer earthing, but the problem is the GI strip used should be of sufficient size while copper strip used can be of reduced size, so places where space constraints occur, copper strips are used, moreover economical considerations are also important in chosing the strips. It won't affect the transformer performance if GI is used instead of copper.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
PLEASE TELL ME ABOUT QUESTION PAPER OF UPCL ENTERENCE EXAM.
Testing procedure of DG alternator stability test
what is th basic difference between a d latch time line and a d flip flop time line???
what is the importance of earthing system on the generators big capacity and small?
What is cathode ray oscilloscope (cro)?
nwhat are the main Components of servo motor?
Explain Creepage Distance of Insulator
howmany electrician should maintain for a 1000 kva used plant... in kerala..
how to calculate the distance relay faulty zone?pls explain?
what is the necessary of using inductance property in transmission lines even through resistance is used to opposes the high current flows in that?????
What is K-rated transformer? What is the use of it? What can be the size(pls provide calculation if possible) of K- factor transformer for 550kW,690V motor operating with drive (VFD)?
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to confirm its base capacity?
Swg formulae
what is booster? and how it is connected in a circuit?
IN SINGLE PH TRANSFORMER IF LEKAGE IMPEDANCE DROP IS NEGLECTED ,THE FLUX IN THE MAGNETIC CORE and the lekage flux linking a winding are a)proportional to the applied v to the winding i respectively.