why transformer rating is in kva?

Answer Posted / m.gopinath

All ac machines rating is mentioned in kva on name plates
where as dc machines rating is mentioned in kw. In the case
of dc, there is no question of pf as the loads for dc are
always resistive in nature and the pf is always unity. But
in the load can be resistive, inductive or capacitive in
nature in case of ac machines.

Let us calculate current for different loads (ie for
different pfs) in case of ac machines if their rating is
mentioned in kw:

16 MW (not in MVA as in normal case), 132/33 KV T/F

Case 1: For resistive load

HV Current = 16000/(1.732*132*1)= 70 A (approx.)

Case 2 : For inducive/capacitive load at 0.8 pf

HV Current = 16000/(1.732*132*0.8)= 87.5 A (approx.)

observe the above two cases, for a given rating in MW(16 MW)
the current is quiet different and it will depend on the
nature of the load on T/F. This is not in the case of DC as
the nature of load is always resistive.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Is better to supply the voltage for static exciter from the auxiliary power source or from the SG terminals? And why?

1487


Dear Mr B C pal...Can you plz. put some light on principle of operation of Z-Ct in conjunction to its use with 1Cx1000Sqmm HT Cables & Directional Ground Fault / Over Voltage Relays...Regd..Parag v K 9899115632

2244


How can we calculate ac current from the given DC current when AC voltage is given?

1527


What will happen if the d.c. Machine is operated below rated speed?

684


what about the power of wattmeter at starting and loding?

1647






Explain about p.t?

665


Is there any rule to select the voltage of motor based on KW rating? What is the rating above which lt motor becomes the HT motor?.

1224


Dear sir, In our plant have Station Transformer having capacity,i want to know, why LV side 40 - 40MVA is given? & how we can get 6.3 KV supply from tertiary(i.e. Open delta connection), Vector Group YNyn0 - yn0 +d MVA Rating 80MVA / 40 - 40MVA + 26.7MVA Voltage rating 420 (Tap range +6,to -10)81.25% /11.5KV - 11.5KV +6.3KV

1745


hey guys i scored 910 on GRE and 67 on TOEFL respectively.I have an aggregate of about 74%in my B tech.For which colleges should i apply for an MS program in electrical engineering.I am looking for colleges in NJ,SC,NC,GEORGIA, NY. Please reply with a good response.....

1539


What is given by the definition in BIL IMP/PF = 950/395 kV. This was found in a name plate of a power transformer.

1839


Can anybody just suggest about the scope of Electrical design with ETAP software?Just guide me?

3288


I have 2500KVA transformer delta/star,13.8KV/380V provided with LV 4000A breaker. Already I have 2300KW motor feeder with a full load 90%. Is it possible to connect another 1600A from that breaker? If so how the calculation is done?

3365


tell me some type of questions throught which i can prepare for exam and do my best

1548


What is mean by Sensitive Earth fault & what are the effects

3744


what is a power factor?

1316