Answer Posted / m.gopinath
All ac machines rating is mentioned in kva on name plates
where as dc machines rating is mentioned in kw. In the case
of dc, there is no question of pf as the loads for dc are
always resistive in nature and the pf is always unity. But
in the load can be resistive, inductive or capacitive in
nature in case of ac machines.
Let us calculate current for different loads (ie for
different pfs) in case of ac machines if their rating is
mentioned in kw:
16 MW (not in MVA as in normal case), 132/33 KV T/F
Case 1: For resistive load
HV Current = 16000/(1.732*132*1)= 70 A (approx.)
Case 2 : For inducive/capacitive load at 0.8 pf
HV Current = 16000/(1.732*132*0.8)= 87.5 A (approx.)
observe the above two cases, for a given rating in MW(16 MW)
the current is quiet different and it will depend on the
nature of the load on T/F. This is not in the case of DC as
the nature of load is always resistive.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is servo motor and how it works?
what is invertor supply and raw powersupply
Form S and "c" license application both are same? @ tneb portal
how much excitation voltage required to generate 1mw power?
what is the power factor used by the PHCN in nigeria? 2. what is the difference between an alternator and generator. 3. Generation of poweris in KV but how is transmission is in MW. 4.If the transmission of power is 20,000MW how can it be increaesed to 80,000MW
What is dynamo function in DG sets and draw block diagram?
how is control wiring coding is done in a CRP panel ?
How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V
why and how current drawn by battery charger depends upon the altitude where it is located?
I WANT TO INSTALL LIGHTING ARRESTOR ABOVE 20 FEET HEIGHT INDUSTRIAL BUILDING. NOW IT WAS 15 FEET HEIGHT HOW MUCH DISTANCE IT WILL COVER & HOW TO CALCULAT THE DISTANCE COVER BY THE ARRESTOR
Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.
1.what is mean by 8/20 micro sec waveshape
kindly send me 11KV MV motor differential protection procedure by primary injection method.
In what cases (circumstances)we should apply P controller, PD controller, PI controller & PID controller ?
can anybody sent me power grid questions. what subject should i prefer for preparation?