Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to select Main CB Rating for 220 KW Load?

Answer Posted / ashif khan

before the selection,first we should know that it is single
phase or three phase load.in case 1-phase we use p=vicos&#1092; to
find out the load current but in 3-phase we use p=&#8730;3vicos&#1092;.
suppose it's 3-phase then load current=382amp.now add
minimum 25% safety factor to it.then it will be 475amp ,so
we can select C.B of 500amp current rating.

Is This Answer Correct ?    7 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to decide the size of the capacitor for a single phase induction motor say 2 HP ??

2311


if field breaker of generator is closed prior to its rated speed on a power generating unit. what will be the effect on generator, unit transformer and starting transformer.

1808


how to discharge 3 phase power factor correction capacitors

2504


Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m

2883


What is rotary phase converter?

1131


I have a relay contact rated at 220v dc which is supplied with a 24vdc from the panel,for it to trip the dampers(24vdc).What if the application of the relay changes so that it should work at its rated 220vdc then will it work at 24vdc supply given or any other consideration needs to be taken .....

2152


What is the difference between earthing,ground&nutral?

6844


what are carbondioxide and dcp used in fire extinguishers

2097


can i use 4 number of circuit breaker as single phase manual change over switch? if yes then how plz also send ckt diagram at nazimzamurad@gmail.com

2175


How to Preparation of online test

1763


Refernce currents are to be generated using refernce cueernts how can this be done

2318


Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.

2175


how oltc works in rectiformers of higher rating (27 mva,200v dc,120kamps) please provide me full information with diaggram.

2183


The transmission does not have options: a)Partition noise b) Flicker noise c) resistance d) Short noise and reason

2497


Why back emf used for a dc motor? Highlight its significance.

1246