Three set (each phase contain 2 cable of 400 mmsq CU XLPE
AWA) of single core cables are connected to 11 KV motor of
14 MW & the switch gear supplay is taken from 11kv feeder &
this supplay taken from 275 KV substation. Problem is one
pair cable(L3- 2 cable ) getting very hot & gland melted
and damaged in switch gear side. the other two cable
haven't any more hot(ambient temp only & L3 haveing 95- 100
Degree C. The same problem happened in 275 KV substation
switch gear side also where the supply taken for 11 kv
switch gear. But here L2 phese cable had problem. Why it is
happening like this?. The cable having temperature
different at different location from gland side inthe case
of 11KV feeder of 275 kv substation. why ?
Answer Posted / kaviraj
Get a thermal imager or camera, you will see the loose
connection very easily. I also bet it's a loose connection.
Else one of the cable cores has been broken. Check for sharp
bendings on cable. Copper braids still connected/earthed
properly?
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
State magnitude criterion.
what is d check in dg 1500kva
where does 22kv line starts
harmonics filter
Please explain the following and how these are working with PLC unit 1.I/O Module 2.I/O Device 3.Adaptor Card 4.Ribbon Adaptor 5.RS 485-FC
Where I can get the sample question for post of Junior engineer electrical-II For RRB Bhubaneswar.
How we can recongnise the phase displacement of transformer connection between primary & scondary...plzzz explain it with example.........
draw singleline diagram of star to delta and dol starters
explain the Trip supervision circuit
What magnetic circuit is formed in berry-type constructions and why?
what is ic 01,ic 06 ?is it types of cooling?
how to determine ct ratio in ht vcb?
Is there any standard guidelines/Criteria to design NGR/NGT.?
Is there chopping current in resistive circuit
What is the accepted limit to increase the choosen transformer capacity over the load and why ?