which fault current is maximum: 3 phase short circuit, LG,
LL or LLG?? why??
in one of the problems that i have solved, 3 phase short
circuit current on an unloaded generator came out to be
less than the LG fault current. can anybody please explain
why.
Answer Posted / dr rajan
It is always the 3 phase bolted fault. Check your problem
again. You may have made a mistake. Why 3Ph fault current is
high?
When all phases are grounded or shorted, the impedance is just
let us say X in each phase leading to V/X x 3 times. where as
when you have LG, you will include the line impedance in
series with X, equals X+xL, which is more than X on 3Ph short
ckt. When you divide V/(X+xL) what will you have???? More
current or less current???????
Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
Which motor connection is preferable star-delta or delta-star?
What is core CT & it's function?
Why does increasing the magnetic flux in the main field of a d.c motor cause the armature current to reduce??
What is the BS(British Standard)code for 11kv motor
why we can use 1 to 5V dc
how to Select its CORE in electrical cables based on its applications? or Application of various types of electrical cable based on it CORE?
How to Calculate the Fault Level of Electrical Installation
Can i replace Earth leakage relay to the faulty Earth Faulty Relay
what exactly commisioning work does in electrical site work... LT side?..
Pl. share your experience about industrial-electronics repair of machine tool.
which type of cabel
Dear all, I just want to ask an expert on this forum for some insights. For the magnetic balance test, when applied voltage on a Delta-Star transformer e.g. Dyn11, the following relationships apply for HV side: 1. H1-H2 = H2-H3 H3-H1 2. H2-H3 = H3-H1 H1-H2 3. H3-H1 = H1-H2 H2-H3 For the LV side also: 4. X1-X0 = X2-X0 X3-X0 5. X2-X0 = X3-X0 X1-X0 6. X3-X0 = X1-X0 X2-X0 Is there a similar pattern for Y-d, Y-Y, D-d? And how about Y-z, D-z, Z-y transformers? I've tested a YNzn5 transformer and for LV side I don't see the pattern. In this particular case I got for LV side the following (see values below): H1-H0 H2-H0 H3-H0 X0-X1 X0-X2 X0-X3 128.0 119.9 7.2 29.2 13.3 15.8 70.7 128.4 59.2 23.4 22.0 3.6 7.2 120.1 128.1 13.4 29.3 15.8 What is the relationship here for LV? For row 1 I see the relationship, for row 3 I also see but it's shifted, but for row 2 I don't see such relationship. Any suggestions, answers, someone?
Why water bubbles when D.C. Current is passed through it? Why not when A.C. Current is passed?
What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.
What is the actual calculation for transformer short circuit test?.