why are the likely reasons for bochholz & pressure relays
oprate due to a internal fault but not differential relay ?
Answer Posted / yusuf
Buchholz and Pressure relays such as Over Surge Relays are
also known as Gas operated relays... Consider an internal
fault such as inturturn fault in the transformer winding,
then the oil temperature raises which in turn produces Gas
inside the Oil Tank.. This Gas passes through the pipe
connected between Oil Tank and Conservator Tank and relay is
placed in the pipe work... so the Gas passes through the
relay and gives an alarm first and then trips the
transformer when the fault is severe.... Differential
protection is based on the principle of Differential current
which compares the current at the two sides ( LV & HV )of
the Trafo... And that's the reason the Differential
protection does not operate for incipient (Slow developing)
Faults
Is This Answer Correct ? | 9 Yes | 0 No |
Post New Answer View All Answers
i applied for the ap transco please forward the freqventley asked QA
How test for Ddo vector group test condition?
What are the differences between single phase and three phase?
WRITEDOWN FEW RELY CODES
temp of cast resin 1500kva tx formerwent up to 138.c but came down very fast to about 100.c within 20 mins when load was reduced from 70% to 60%
i need project topics along with circuit diagram in the electrical and electronics engg and also some websites regarding projets.
how we will deside the high voltage value
What is the diff. between single compression and double compression gland
When MICC cables used ?
what is there inside an inverter and how it works?
Define phase cross over?
I want formula to calculate cable size as per load given in length & amp. I searched many sites but didn't right answer. Please reply me asap.
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
WHAT KIND OF LIGHTENING PROTECTION SCHEMS CAN BE ADOPTED FOR THE FLAT ROOF OF BIG DIMENSION.
How will polarity test of Dy5 Transformer ?