what is procedure of calibration of remote seal
transmiter, botom to top flanch 850mm, fluid liquid
density .73, transmiter fixed on a fractionation colum,
under vaccume 10mbar
Answer Posted / aftab ahmed mazari
If you installed the remote seal transmitter at flanges,
then in case empty tank /vessel, the transmitter will
showing -mA. so do the followings:
1. Make transmitter 4 mA in this case(without any pressure,
only lower low leg remote seal pressure acting)
2. Apply 850 x 0.73 =620.5 mm of water to high side of
transmitter flange and set transmitter out put 20 mA.
aftabmazari@yahoo.com
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What are different types of cable?
why we r opening HOT BYPASS valve during startup of a compressor?
Describe the function of Accumulator into the Pump
Draw a group of instruments interlocked to a Pump & Motor?
WHY THE DEGREE OF VALVE PLUG AND VALVE SEAT IS SLIGTLY DIFFERENT I CONTROL VALVE TRIM DESIGN
Q- What are the application in which PNP transistor is preferred over NPN ?
what is piezoelectric transducer?give an example in power plant n state its principle?
Describe the typical instrumentation used in monitoring the performance of a shell and tube heat exchanger.
What is the use of double seated valve?
what is span value and zero ? and how set ?
Why all the drains(Gland sealing,ESV,Casing inlet etc) are directly connected to the flash tank instead of hotwell of the condensor in the power plant? My Email Id:naba02222@gmail.com
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
why we are using magnet for calibration of gas detector?
How earthing can be checked????
all questions related to instrument technician in any offshore oil and gas company.