How to Calculate 11 KV Side Cable size of a 250 KVA Oil
cooled transformer
Answer Posted / a.narasimha rao
Transformer capacity is 250 KVA
Primary current = 250000/1.732x11000= 13.12 Amps
Short circuit current ( 6 times primary current )
total current would comes -----90 amps
Size of the cable --- 3c X 35/ 50 sq.mm 11 kv HT XLPE
cable is required for primary
Secondary side current -----333.35 amps
cable size is 3.5 c X 300 sq.mm AYFY cable is required
Is This Answer Correct ? | 23 Yes | 15 No |
Post New Answer View All Answers
Explain what is electric traction? Explain few advantages of electric traction system?
Why hydropower stations are preferred solution for meeting peak loads in grids?
why burdens of VTs is more than CTs?
What is a DC series motor?
What is difference between isolator and circuit breaker?
What are the insulation standerds for eg H clase and how many insulation standerds are there and its standerds??????
how to measure the current by compact digital equipment with dislay which fit inside any equipment
Define liftable weight of a transformer? Does the total weight of transformer include oil weight?
What is depreciation factor?
I have made a 3 phase thyristor full bridge rectifier. But at the moment it is working only for the half bridge operation. Both the half bridges are on operation separately but when i put it into full bridge operation the oscilloscope output is zero. I rechecked that the pulses are correct for each thyristor. what could be the possible reason for this?
current transformer balance the power level on both sides. e.g in case of step up, at secondary side voltage rise but current decrease and vice versa in case of step down transformer. but how this power level remains same in case of current transformer and voltage transformer
How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V
wht is embedded systems? what is new inthis field?
hi i have applied for lic of india south cenrtal zonal ,hyd. i didnt get hall ticket till now.let me know how can i get form internet
A 500 V shunt motor runs at its normal speed of 250rpm when the armature current is 200A. The resistance of the armature is 0.12 Ω. Calculate the speed when a resistance is inserted in the field reducing the shunt field to 80% of normal value and the armature current is 100A.