Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Are same transformer be employed for step up and step down
services?

Answer Posted / bajrang ahirwar

NO
same transformer can't be used for both operations.
exception is ICT like 220KV/400KV
ICT is inter connecting or interposing transformer, these type of transformers are specially designed.
there no load an on load losses ane calculated so that they can be operated from either side.

on the other hand if have a 2000 KVA 11kv/440V 0.85 pf step down transformer:
current in hv side will be = 123 A
and current in LV side will be =3087 A


the secondary has to bear heavy current so it is designed accordingly with Thick winding.
and HV Primary has to carry a comperatively low current so its windings are of thin windings.

NOW the reverse operation

the heavy winding will be connected to high Voltage 11 Kv side, fine no problem, because it has to carry a lower current of 123 A ans secondary is rated for 3500 A approx.

BUT
the thin wired high voltage winding will now have to supplly the larger gurrent 3080 A, this winding has also larger losses R=Rho L/A
result??
the winding will burn out.

so practically it is not possible.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the difference between surge protection capacitor and surge arrestor

2377


Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?

1853


How do i right a ladder diagram that has 1 actuator that performs a full stroke followed by a half stroke

2145


What is the tipical Online UPS input voltage for 20 KVA load ( 3 Phase or 1 Phase )? Why ? Explain it...?

2694


When will you multiply and devide with derating factors to the actual value while sizing the cable?

1986


we can run 2phase as 3phase .what will be the differnce with respect to phase angle, power, current between the two modes

2308


how to compare with Relay settings for HT< panels, RMU panel, and PSS CSS transformer?? 1) Load amps, 2)Tripping time, 3) CT ratio, 4)Cable size 5) Transformer KVA rating 6) transformer full load amps

1323


what is diff. between earthing grid,earthing mess, earting grid?

2451


Yazaki india pvt ltd interview questions qurey related

1084


In diesel generator how AVR get voltage to excitation. And basic diagram DG EXCITATION CIRCUIT.

3379


why T/F winding temp measurement cts are odd secondary current ie,109A/1.2A/1.4A?

1923


what is the purpose of shading ring or shading coil in electrical equipments.

4539


What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.

8402


sir i had plane to do some project with the base of hopkinson test in AC supply its possible

1922


why transformer ratings in kva? & DG ratings in kva? & Motor ratings in kw/HP?

1564