In thermocouple could we use the lug for termination or
not,Thermocouple is any time,I am currently concerned with
K type.please let me know if anybody know
Answer Posted / george mathews
The basic principle behind any Thermocouple is that there
are two disimilar material connected at one end that is
called the Hot Junction , and we take our out put from the
other open junction that is the cold junction. But when we
connect a lug there is anather metal thats mean 3 metal and
we ll definitely get a wrong out put and in a high
temperature area or zone this may make a big difference.
| Is This Answer Correct ? | 14 Yes | 5 No |
Post New Answer View All Answers
How can measure flow in oil line?which type of transmitter is generally used?
How does work A temperature valve or fv control valve in process plz brief me
What is first echo & echo window in radar type level transmitter?
What are different types of control valves?
can you provide me full detail about instrumentation in ONGC??
why I need valve guard and whats different between guard and positioner ??
why would you like to join our company
Which type of diaphragm use in costic line, dm water line, natural gas line, oil line?
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
Calibration procedure for water rotameters
where proximity sensor installed on tank in loading arm application
how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?
Which types of quections asked in interview for FORMULATION PLANT (PHARMA)
Gas equation
Identification of control valve parts.