I want formula to calculate cable size as per load given in
kw & amp.I searched many sites but didn't right answer.Plz
reply me asap.
Answer Posted / tauqeer hussain
We can use fromula for Voltage Drop Calculation
VD = mVxIxL/1000
VD = Voltage Drop
mV = Milli Volt(Given Rating Cable Manufacture)
Example 16sqmm mV =2.5 mv/a/m
I = Load Current
L = Lenght of Cable
Exapmle #
Voltage = 415vAC, Ampere = 25, Length of Cable = 100Meter
VD = 2.5x25x100/1000
= 6250/1000
= 6.25 (in volt)
= 1.50% (in percent)
| Is This Answer Correct ? | 35 Yes | 8 No |
Post New Answer View All Answers
how u measure/calculate renge of capacitor,capacitor has no any rating tag.what is the theory of measure of capacitons.
Please define ampere?
What is inrush current?
How to Decide(calculate) Bush bar size for copper and aluminiam ?
High speed earth switch operation with diagram
How we can recongnise the phase displacement of transformer connection between primary & scondary...plzzz explain it with example.........
How do I calculate/select Droop CT ratio for various capacity of generators?
what will be the effect if you were using different brands of outlets?
Why we use Electrical energy rather than any other type of energy, mostly? Explain behavior of open secondary CT and short circuited secondary PT in energized condition?
advantages & disadvantages of Lagging and leading power factor .
why the colour of insultor stack , petticoat is brown. Is it has some technical reason.
advantage and disadvantage of team work?
What is the need of generator relay panel
Why single phase induction motors are not self starting ?
When color of silica gel will gets change from blue to pink from Top to bottom?