what is the current rating of 2500 KVA,33KV/433v transformer
on secondary(LT) side
Answer Posted / kaami
power in = power out
v*i = v*i=2500kVA
on input side
33kv*i=2500kv
i=2500/33=75.75amps
on output side
v*i=2500kva
433v*i=2500Kva
i=2500/433=5.7ka
so it is designed for 5.7KA on secondary side
| Is This Answer Correct ? | 19 Yes | 22 No |
Post New Answer View All Answers
State kirchoff voltage law?
for 4 MVA , 33K.V/6.6K.V transformer. secondary side the connected load is 3000H.P. What is the rating of capacitor bank to be insttaled.
how much maximum load a 2 core (Single phase) 16mm aluminium wire can take ?
What is the effect of positive feedback on the stability of the systems?
TYPE'S OF BREKAR ,WHAT IS TRANSFORMAR & SAFTY. STARTER DOL & STAR DELTA STARTER.
what is mean by transition resistance of transformer?
give single line diagram of D.G distribution form alternator to main L.T panel?
How much load can take a 16 mm aluminum cable 3 phase
We normally make oil soak pits under Transformers. Oil from soak pit goes to collection pit. We provide granules/pebbles under transformers. My question is weather granules/ pebbles to be filled in soak pit or not? if yes upto what level?
what is smartµ grid technology?under coal gassification?
how to find the Motor,s insulation Power?
What is the maximum No. of out going mccbs permitted from an LV distribution paqnel? What is the ampere relation between incomer and out going switch gears/mccbs?
How does an induction motor start?
Mention the methods for starting an induction motor?
we have earthmat at 110KV substation.we would like to take earth resistance.b some says that by connecting earth megger terminals (C1,P1) at middile point of earthmat (at riser) will cause voltage gradient at other earthmat nods and dont get exat earth resistance.when connecting at end nods will get exat value . is it correct .please explain