calculate multiplication factor of a trivector meter with
line ct ratio 200/5A, line PT ratio 11000/110V and meter CT
ratio 200/1A and meter pt Ratio 11000/110V.
Answer Posted / k.prakashchandra
If the line CT were of 200/1 ratio, the meter would read
correctly. As the ratio is 200/5, for 200 A primary current
the sec current will be 5 A instead of 1.0 .Hence you have
to divide the reading by 5 ,if it is capable of taking 5A.
| Is This Answer Correct ? | 9 Yes | 3 No |
Post New Answer View All Answers
What is the control action?
how to calculate the capacitor to maintain power factor?
what is the Earth Voltages in Power Plants, Sub-stations, Industries, Residential & Commercial Buildings.
How many devices can be connected in one zone of FACP
pre arcing time of ehv breaker
how to CHECK CT AND PT AT THE FAULT OCCUR IN GENERATOR RELAY PANEL .
i am in need of AC SYNCHRONUS MOTOR 30KW. ANY ONE KNOWS THE MANUFACTURER OF SAME. ALSO MOSFET AC CONVERTER 20KVA CONT.OUTPUT.
please send me RRB electrical engineer previous year questions for Sr. Section Engineer
The inventer is a battery, but if lost current at home u will turn on the fan but the is AC and inventer battery is dc . Then how the fan was rotating. What device Or machine in fan converst the Dc power to Ac power
what is the reason the main breaker is trip during the motor is running? (some time the breaker is not trip)
What are the disadvantages of autotransformer?
if we run a 3 phase machine on two phase what will happend??? given answer with solid reason please
What is the working principle of MIG welding? and its out put Voltage?
How can you sized or estimate the ligthning arrester current rating?
what is the calculation involved to design the heater to heat 10KL of water in temperature control unit?