calculate multiplication factor of a trivector meter with
line ct ratio 200/5A, line PT ratio 11000/110V and meter CT
ratio 200/1A and meter pt Ratio 11000/110V.
Answer Posted / k.prakashchandra
If the line CT were of 200/1 ratio, the meter would read
correctly. As the ratio is 200/5, for 200 A primary current
the sec current will be 5 A instead of 1.0 .Hence you have
to divide the reading by 5 ,if it is capable of taking 5A.
| Is This Answer Correct ? | 9 Yes | 3 No |
Post New Answer View All Answers
Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example?
Advantages of using generator circuit breaker (GCB) scheme in a power station ?
Advantage of LT panel vs HT panel
How can I calculate ISF of current transformer?
What are the conditions to be satisfied for parallel operation of dc generators?
What are the difference between normal application Transformer and Solar application Transformer?
Readings of ER300P Trivector meter
in my working site. momentary jerck in electrical supply ocurred frequently which cause of multiple losses in our electrical equipements. how can we protect our electrical machines and equipements in this situation.
is it possible to say motor horsepower number without seeing name plate(when name plate damaged)
How can we checked Killo Watts of Motor & Alternator?
What is the difference between resistance grounding system and resistance earthing system?
In india, according to trade theory above 5 HP motor reqired star delta starter. But we R connect 11 KV motor with 14MW in Direct to line ( With VCB starter combination) Can U Guess, How it is possible ?????
TCS IS IT COMPANY THEN WHY DO THEY NEED ELECTRICAL &ELECTRONICS ENGINEERS?
sir, Is their any measuring unit of knoking? please explian?
PAC and simple Ac different