What should be the ideal tapping location for pressure
differential transmitter for liquid service. If the tapping
taken from the top of the pipe then PDIT will work properly
or not. If PDIT do not work properly then what minimum
corrective action should be taken in order to solve wrong
tapping locations.
Answer Posted / nilesh
1.Ideal tapping location for liquid flow transmitter
orifice tapping in horizontal line is horizontalplane or 45
Degree downwards.
2.If tapping taken from top of the pipe then gases in
liquid service can disturb the measurement and hence
control.
3.Tamperory solution for fluctuation is frequent flushing.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
What is Cavitation in a control valve?
what is RTV function in in process control?
Can anybody tell me how to select the size of earthing cable for DCS & PLC system.Please tell me any relevant answer here or mail it to me.
what is the usage of QDV & VOLUME BOOSTER
What is zone,loop/fire alarm system?
how to calibrate and troubleshooting of leveltroll?
Which language of programing is popular? how can i learn it ?
Difference between 2-Valve Manifolds, 3-Valve Manifolds and 5-Valve Manifolds 3 with diagram
what is exact time to study dcs and plc cources
this site is owned by an nonsense
what is loop1 and loop2 in MTS LT?
How u measure the massflow in orifice flow measurement techniques
Hi, I am Newely Joined in Construction company instrument engineer? Any one can Plz tell me How can I advanced preparation for Releated Engineering and construction Documents?
what are procedure of sox-nox calibration
How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.