We have laid the single core Armoured cable 7 nos ( 2 each
phase & 1 neutral ) to cater our electrical load .
the issue is though we have Glanded the cable both the end
also givan the earthing to the panel both the end we are
facing a heavy sparking at the gland side. what could be
the reason.
Answer Posted / abhishek mishra
Dear Virendra
if you are using CRCA gland plate for glanding then such problem may occur. If you are using single core cables then either use aluminium gland plate or make a thin cut hole to hole in CRCA gland plate
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Can anyone tell the proper diagram of star delta starter????
at work i have a genertor/alternater what is the easyest way to work out if it is dc or ac?
block diagram of 2 ups system connected in parallel mode?
control & auxilary circuits used for circuir breakers
what types of cable used in underground coal mining?
what is mean by restructuring power system?
how we calculate torque ? how we improve it ?where torque will either motor or generator ?
Why synchronous motor is used in power factor improvement,dc series in lift
Why we are using only Dyn11 tranformer in distribution system but not using a Dyn1 in distributing system?why not and advantage and disadvantage in both
How to design the NGR Resistance
THERMAL CAPACITANCE IS MEASURED IN..................................................
what is transient enclosure vltage , very fast transients, very fast transient over voltages
How to Calculate The sag of OPGW in Transmission Line???
Could Please Explain briefly. Why used stabilizing resistance series with High impedance bus differential protection relay.
what is deffrence between squirral cage and wound rotor in IM?