If a differential pressure transmitter is calibrated for
0~2500 mmH2o and transmits a 4~20mA dc signal. The
transmitter is placed across an orifice plate which is sized
to create 2500 mmH2o differential at 5000m3/Hr
a) what is the flow rate when the transmitter signal is
13.0mA DC?
b) what is the signal output of the transmitter when flow
rate is 2500 m3/Hr ?
Answer Posted / nani babu
a) flow rate for 13mA is 2812.5 m3/hr
b) 12 mA to 2500 m3/hr
| Is This Answer Correct ? | 24 Yes | 6 No |