we have consol make 3 phase servo stabilizer for cnc m/c.
while installing the earth neutral voltage is 1.7 volts at
stbilizer off condition and when stabilizer get on en
voltage reaches 4.8 volts (new earthing is done and neutral
is helthy condition all phase to neutral volts 440,442,441
v)why this happen.solution for cause.

Answer Posted / vishal ingle

Problem looks like in the type & quality of earthing
electodes and pit specifications. if possible try for
another earthing pit with proper watering arrangement.
Note : the earthing pit should be in mother earth & not in
the backfilled soil. (Earthing quality varies with the soil
strata i.e. BC Soil, Hard rock soil, Muroom etc)
Further the earthing pits may be interconnected also to
obtain stabilised results.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are the specifications for getting approval of Substation?

1430


What will be the fault current of any system when its generation is 10% of BASE generation( FUll Load )?Will is 10% or the same as full base calculation?

1432


How to test IR testing & magnetic balance test

1496


How we can calculate the Amps for the cable Ex:- For 1sqmm wire how many amps we can draw (calculation)

2742


Practical condition in 400KV Sub station:- Breaker(open) , isolator(open), Earthing (close) at both end e.g A & B. Now Open A Stn Earthing than Open B stn Earthing (Which have a 50MVA reactor) , AND suddenly show R,Y,B phase 704KV,573KV,118KV respectively. Que is without closing of breaker how it is possible.???? My Whats app No:07621840498 for Further Discussion. Pls experts suggest.

1598






why constant voltage transformer should be start without load? and if started then what will happen?

1618


HOW TO CALCULATE EARTHING SIZING?

1565


EXPLAIN THE TERMS "INTEREST AND DEPRECIATION" AS APPLIED TO ECONOMICS OF POWER GENERATION.

1772


What is the formula for calculating no-load current?

650


State and define norton’s theorem?

785


Can we transmit digital signal to long distance ?

1484


I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA

2540


what type of questions are asked and howmwny questions belong this catagory?

1720


why the carbon brushes are broken in srim while the motor runningtime

1249


will 1050kva DG set withstand for back charge of 16MVA transformer

1464