Answer Posted / noel
You should check that the alternator is aligned properly
with the generator motor. this should be done according to
the manufacturers specs. Rotate the alternator and check the
gap between the rotor and the stator. Also this should be
provided by the Manufacturer. Then take and IR and PI test
and record your findings. Check that the data is on the
right parameters. And also check the wirings for the CTs.
Depending if they are European or US manufactured the flow
of the current may vary a give you incorrect trips during
commissioning.
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
what are the applications of PLC?
what are problems caused by the pdu in rack server
in 1-phase 230v,how in 3-phase 440v. in each phase in between 230v.
where we use the SFU & FSU?
What is creepage distance..... what will be the value for different voltage level
How to calculate the volumetric capacity of a oxygen & Nitrogen gas Cylinder if pressure is 145 kg/cm2 & water capacity of cylinder is 67 liters.
how to calculate cable size in diffrent loads?
What is cut-off rate?
How to Calculate Transformer Earthing Electrode Rod Size both Body and neutral Earthing ? Any Standard Formula? Please Suggted
Name two types of electrical analogous for mechanical system.
hi frnds...pls send me aptransco previous papers .....pls..pls,,,(madhar.rocking@gmail.com)and suggest me some websites
Why do we apply both Differential and REF (HV and LV) protection schemes on YNyn configuration of a transformer?
What is the difference between shortcircuit current, rated current of cable & MCB with example? What will be the size of cable required for 5.5 KW motor (Full load current 10 Amps approx.), Starting current with DOL is 120 Amps. Aprrox. Short circuit current with LLLG fault is 2000 Amps Approx.
DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.
use of choke in APFC panels