Answer Posted / noel
You should check that the alternator is aligned properly
with the generator motor. this should be done according to
the manufacturers specs. Rotate the alternator and check the
gap between the rotor and the stator. Also this should be
provided by the Manufacturer. Then take and IR and PI test
and record your findings. Check that the data is on the
right parameters. And also check the wirings for the CTs.
Depending if they are European or US manufactured the flow
of the current may vary a give you incorrect trips during
commissioning.
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
what is diff btw electric,magnetic & eletromagnetic field
defult setting in p220 micom motor proction relay for 11kv,640kw,f.l.a.-40a,1440rpm ht motor?
can you plz send l&t aptitude questions if available its urgent plz plz plz
DESCRIBE THE CONSTRUCTION ANDOPERATION OF BELT CONVEYORS AND SCR CONVEYORS , DRAW NEAT SKETCHES
Explain advantages of storage batteries
Is there any standard guidelines/Criteria to design NGR/NGT.?
How will you justify IR value and Charging voltage of any motor,transformer and Cables.......???? . . . . . . . . Plz tell me any body Baljeet Singh, engineer_89@refiff.com
what is resver in electrical enginnering with answer
How is magnetic leakage reduced?
how we decide the require size is this for a known current at fuu load?
How to design pavement quality concrete by using C.R.C.P Method
Define coil span?
State kirchoff current law?
I have 2 KW electric water heater.I am gonna use it in controlling water temp.so I needed to increase or decrease the heating capacity.is there any electrical-electronic circuit for varying the resistance & so current?
Can any answer me ,What will be the range of C.T coil for L&T energy meter EM301 used for 180 kva DG set