What is the Different between CT Class-0.2 & Class-0.2s ?
Answer Posted / sam
Accuracy class of 0.2 means +/- 0.2 % error. But, the
declared accuracy is guaranteed only between 100% & 120%
rating. And, with some increased error, the CT performance
can be guaranteed from 5% loading. Below this load, the
error is not guaranteed. It can be anything.
Normally these classes of accuracy are used for Tariff
Metering by the Utility Company.
In large industrial projects, the project would be
commissioned in steps only. In such a case, initially the
loading will be very low. If the tariff metering CT errors
are haphazard, it may not be acceptable either to the
supplier (in case of negative error) or to the consumer (in
the case of positive error). And the magnitude can be quite
large, say, with a sanctioned demand of 10MVA, even 1%
error means 100kVA.
To cater to such situations, Standards have introduced two
new accuracy classes, 0.2S & 0.5S for tariff metering
purposes. These special CTs guarantee the declared
accuracy, even with 20% loading. And some definite error
can be defined even with a load as low as 1%. Thus they are
suitable for industries where loads are commissioned in
steps or stages.
| Is This Answer Correct ? | 44 Yes | 5 No |
Post New Answer View All Answers
Name two types of electrical analogous for mechanical system.
What is the function of the generator exciter?
List advantges of active filter over passive filter?
What should be the height of basement according to NBCC code?
While testing a ZCT what parameters have to check or measure?
What will happen if the d.c. Machine is operated below rated speed?
how does this job compare with others you have aplied for?
how can i improve the power factor in domestic (230v)
Can i replace Earth leakage relay to the faulty Earth Faulty Relay
What are unstable systems?
what r substations?what r there work?why voltages r incresed and then reduced during distribution of power
1. what is usage for power factor in industries?? 2.why we need to monitor power factor??
Is there a diode made that works with AC 120 volt 20 amp? If so can it completely stop all current flow in 1 direction at all times?
a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn
i am gng to visa interview this july i have 4 backlogs gre 1010,toefl 75,pls give me the tips pls pls