An 11kv system consisting of an underground cable to a sub
station about 300 meters away was shut down for about 10
hrs. On energising, it tripped off on earth fault about
10---20 mins later 6 times but since than it is not
tripping.its already 3 weeks now. The SPAJ was found to be
fine. what could be the cause.No test had been done to
determine the cause of the trippings till now because of
demand.
Answer Posted / k.prakashchandra
If only you had replaced the breaker cubicle and test
charged you would have come to conclusion.If the all 3 poles
do not close almost at the same time and there is a time
gap, the breaker is likely to trip on EFR due to the
unbalanced current in case of 2 OCR + 1 EFR protection
scheme.In such cases it is advisable to test charge on no
load during the second time and confirm the mechanical fault
which is not consistent & does not occur always.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What is different between Circuit breaker and Isolater?
List the power rating of any 5 important electrical appliances used in houses.
What happened ,If 3 phase clearance not maintained in 33KV Line,11KV LIne etc?
Explain about Dubai electrical sysaem? Explain about Dubai drinking water system? Explain about Dubai Burj tallest building Electrical,Water.etc.. maintenance system?
I WANT BHEL PREVIOUS QUESTION
what is differant beetween overload current and phase current?
What should be setting for alarm,tripping and cooling fan on for power transformer's oil temp. and winding temp. indicator?
we have 15 ampere variyac but we want 30 ampere variyac what we do
Brief working principle of stabilizer,application & safety precautions
What is the difference between acs 550 & acs 850
Is it true online ups having bypass mode if it is true then why we called ups because it is interrupting power when goes in bypass mode
What is Surge Capacitor? Why it is require in Generator Circuit Breaker,inspite of surge arrester?
Difference between shunt, PMG and AREP excitation. Which is the most reliable between PMG and AREP.
What is inrush current?
what may the reason for vector shift in a generator?