how to calculate knee point voltage of current transformer?

Answer Posted / arup

Knee point voltage, Vkn = (VA X ALF)/ In

VA= Burden =30 (Say)
ALF= Accu. Limit. Factor = 20 (Say)
In= Rated Secondar Current =5 amp (Say)
Then Vkn= 120 volts

If CT Ratio is 2000:5 then In=5
Class is 5P20 then ALF=20, P=Protection CT

Is This Answer Correct ?    37 Yes 10 No



Post New Answer       View All Answers