Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate knee point voltage of current transformer?

Answer Posted / ramesh

to calculate knee point voltage of current transformer by
formal
Vknee point = Isecandary(Rct+ Rcable+ Rburden)
where
Rct= resistenc of current transformer
Rcable =resistenc of cable =2Rcable
Rburden =burden of relay
IF Vknee point< manufacture voltage of current transformer
current transformer is good
IF Vknee point> manufacture voltage of current transformer
current transformer must be change

Is This Answer Correct ?    3 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?

1965


Why L.T.Cable voltage rating is 1.1kV,where as system voltage is 0.415kV?

2343


can u please mail me the syllabus for GET exam for damodar valley corporation?

2072


what is level 2 automation?

3149


Hi all I had applied for the RRB test in the ELECRICAL category. I would be pleased if any of you can sent me previous year question papers. Please forward the question papers to varshashahi@yahoo.com Thanks and regards Varsha

2186


Is it true online ups having bypass mode if it is true then why we called ups because it is interrupting power when goes in bypass mode

2028


The D.C. spark test is applicable to single conductor cable & assemblies of insulated single conductor cables without insulation shield,metallic sheath or metalic armor?

1849


Can i replace Earth leakage relay to the faulty Earth Faulty Relay

1515


In india, according to trade theory above 5 HP motor reqired star delta starter. But we R connect 11 KV motor with 14MW in Direct to line ( With VCB starter combination) Can U Guess, How it is possible ?????

2139


Thumb rule of cable size(rm>30 rm)X multiplying factor=ampere

1608


What is the use of mc( moving coil) in dc voltmeter and dc ammter and what is the use of ( moving iron)in ac voltmeter nd ac ammeter

2885


For a stable system, where should the poles of a system be in a root loci plot?

1230


determine two methods to find loose connection in operational electrical system?

1682


132/6.6πš”πšŸ πšπš›πšŠπš—πšœπšπš˜πš›πš–πšŽπš› πš—πšŽπšžπšπš›πšŠπš• πš‘πšŠπšœ πš˜πš—πšŽ πšŽπšŠπš›πšπš‘ πš™πš’πš πšπšŽπšπš’πšŒπšŠπšπšŽπš. 𝙸'𝚟𝚎 πšŠπš—πš˜πšπš‘πšŽπš› πšπš›πšŠπš—πšœπšπš˜πš›πš–πšŽπš› 𝚘𝚏 6.6πš”πšŸ/415𝚟 πšŒπšŠπš— 𝙸 πšŒπš˜πš—πš—πšŽπšŒπš πš—πšŽπšžπšπš›πšŠπš• 𝚝𝚘 πšœπšŠπš–πšŽ πšŽπšŠπš›πšπš‘ πš™πš’πš 𝚊𝚜 𝚘𝚏 13/6.πš”πšŸ πšπš›πšŠπš—πšœπšπš˜πš›πš–πšŽπš›?? π™Έπš π™½πš˜.. πšƒπš‘πšŽπš— πš πš‘πš’??

977


what is the effect of change in supply frequency on load angle of synchronous motor,all other parameters remaining same?

2349