Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

At site, we have 30Kw motor (3 phase, 400V,50Hz) and FLC
54A as per the nameplate. At the time of starting it draws
840A instead of 390A (7.2%). As per the data sheet also its
390A starting current. it thru a dol starter from the MCC.
can anyone tell what is the problem in the motor

Answer Posted / wani y.s.

First Check the healthyness of the motor -

1. Check the winding resistence
2. Check insulation resistance using megger.
3. Check the bearing and apply the lubricant as applicable.
4. Check the healthyness of connected load.( It should not
locked etc.)
5. If all above is OK. Then remove the motor from load &
ensure it is starting in ideal condition.( Hope connections
you are following up as given on the nameplate)
If it is starting in no load that means load GD squre is
high. Motor is taking longer time to start.You have to
select proper heavy duty DOL starter to withstand the
longer starting time. But ensure that motor is having
thermal time capacity to withstand this time.
7. You can also go for VFD as a starter this will definetly
will solve your problem no need to take care of thermal
time of the motor. Only select proper VFD to suit starting
torque of your application.

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to define Kirchhoff current law and voltage law along with simply examples.

1819


what is v/f control in VFD?

1596


Please nybody say, weather the result of Bharat Oman is declared or not? Probable date of declare???????

2048


which VFD is better ( LT or HT)

2113


What is instrumental error?

1236


How to measure size of cable on a given load

1905


what sort of general awareness questions are asked in o.n.g.c entrance exam?????????????????

4693


at what rate the micro controller increment its timer....is it 1micro seconds or 1/(12*10^6) seconds

1841


Do you need any help with FEWA Electrical Supervisor exams?

1056


what is meant by moulded case circuit breaker ?

2234


how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.

2472


how to electronic energy metter failed in electomagnectic fild passing in the metter and which thing to defect more on metter.

2030


how much cable size required for 70 kilowatt load.

1740


How to decide and select the different earthing wire size for the different types of earthing

2330


how to calculate insulation level of transformer?

1750