Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

At site, we have 30Kw motor (3 phase, 400V,50Hz) and FLC
54A as per the nameplate. At the time of starting it draws
840A instead of 390A (7.2%). As per the data sheet also its
390A starting current. it thru a dol starter from the MCC.
can anyone tell what is the problem in the motor

Answer Posted / wani y.s.

First Check the healthyness of the motor -

1. Check the winding resistence
2. Check insulation resistance using megger.
3. Check the bearing and apply the lubricant as applicable.
4. Check the healthyness of connected load.( It should not
locked etc.)
5. If all above is OK. Then remove the motor from load &
ensure it is starting in ideal condition.( Hope connections
you are following up as given on the nameplate)
If it is starting in no load that means load GD squre is
high. Motor is taking longer time to start.You have to
select proper heavy duty DOL starter to withstand the
longer starting time. But ensure that motor is having
thermal time capacity to withstand this time.
7. You can also go for VFD as a starter this will definetly
will solve your problem no need to take care of thermal
time of the motor. Only select proper VFD to suit starting
torque of your application.

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain the purpose of inductor in an electric circuit?

1069


What is the effect of pd controller on system performance?

1063


what is meant by impulse voltage?

1955


WHAT IS MEANING OF Gg & Gg IN hrc FUSE

3215


how we can calculate the efficiency of a diesel generator ?

1631


What are the different types of LT Cables?

1028


how does a liquid starter reduce the starting currents?

2084


if the load is 80 amp for main fuse and 100 amp for breaker so how can we calculate the cable size (cooper ) .

2019


what is RNG in the DG synchronizing by PLC?

2073


Why corona leads to production of Ozone and glow of the color VOILET?

1914


what are the protecyion of transformer & generators

1911


Why does the Solid state Rectifiers for 3-ph brake motors sometimes have 2 & sometimes 3 output terminals?

2045


What is the numerical quantity of sqcm?

1946


Please, if 1kw is equal to 1.25kva; how then do I know how many kva in 7.5kw?

1581


I want to ask that is there any relation between current denesity of copper and material purity. also is ther any standard which defines the standard current denesity of material.

1898