why middle phase should used for earth fault and other
phases used for over current in overcurrent and earth fault
relay?

Answer Posted / vishal ingle

Not necessary to use only the middle phase.
our Back up protection cosist of two overcurrent elements
and one earth fault element.
under normal condition vector (IR + IY + IB) = 0
in fact middle phase is not used for earth fault prot.
Earth fault relay is connected between the star point of
all three phases (after O/C Relay) and the earth. if any
unbalance occurs, the unbalance current will flow through
the e/f relay.

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the use of piston rings in the engine used for a generator...........

1678


What is essential to prove safe isolation of electrical circuit?

617


why the NGR (neutral grounding resistor) always OFF during DG off?

3059


Briefly describe your ideal job?

2546


a simple c++ program to calculate simple interst with its data members as private

1378






how we calculate the dick for a pole?

1702


whats the differece between Exd and Exe

4267


What are root loci?

642


What was the Dg set radiator and lube oil temperatures trip in ACB

1333


how does high earth to neutral voltage affects electronic circuit?

1272


hi plz send me reliance placement papers..i.e electrical technical papers that have been asked in reliance test.

2455


can you send me the placement papers of electrical engg. from companis like NTPC,DRDO,IOCL,HPCL,BPCL etc.?If,plz send as soon as possible.Thanks.

1666


Practical condition in 400KV Sub station:- Breaker(open) , isolator(open), Earthing (close) at both end e.g A & B. Now Open A Stn Earthing than Open B stn Earthing (Which have a 50MVA reactor) , AND suddenly show R,Y,B phase 704KV,573KV,118KV respectively. Que is without closing of breaker how it is possible.???? My Whats app No:07621840498 for Further Discussion. Pls experts suggest.

1570


hi can any body send me syllabus of rrb electrical section engg... and past pepar also of any board...

2122


why we get 2 differnet values for power factor in 2 watt meter method in 3 phase

1357