how to check a three phase induction motor by multimeter &
megger?
Answer Posted / will bg
Prove your meter/megger on a known resistance block. You
should remove any star or delta connection/bridges if at all
possible. If your earth/ground reference is not the motor
frame itself (i.e. a conductor in a cable) then first prove
your earth/ground by measuring on ohms the resistance
between your earth test point to various places on the motor
frame. You should get almost 0 ohms. Now measure your
phase resistances and they should always be fairly equal.
Rule of thumb is 10% variance. Remember the bigger the
motor the lower the resistance. Now on 500 volts DC measure
all phases to earth. Now switch megger to 1000V DC and
measure phase to phase resistance.
| Is This Answer Correct ? | 6 Yes | 7 No |
Post New Answer View All Answers
what are types of encoder
What is the temperature PROFILE OF A FLUID W. R. T. Distance from a sphere to which it is IN CONTACT which is at constant temp.?
how i chosse capacitor bank if my energy meter is 48 kvr? tell me capacitor bank chossen formula?
How much earthing frequency is capable?
why we used dc supply for field in dg set
WILL SCHNEIDER MAKE ACB(MASTERPACT)TRIP ON REVERSE POWER?
If there is major % of Voltage harmonics in the system, how can it be control or reduced?
Following test should be conducted to find out relative polarity of transformenr terminals A no load test B back to back test C phasing out test D none of above
In constant power region of 3-phase IM torque-speed characteristics, if frequency increases flux A does not alter B decreases C increases D none of above
I want to know Electrical Circuit?
what is (+) and (-) in generator field detector stand for?
What is the role of Dedicated earthing in UPS System?
how you taken aotitude test
what is parellel power factor correction?
How we calculate the size of ht cable for any transformer