hello dear
i have faced problem in drum level transmitter.
the problem is when i engrize the meter meter shows 100%
but the actual level 40 or something plz suggest me
Answer Posted / yomama
The impulse tubes must be filled with process fluid or fill
fluid such as glycol. Additionally the specific gravity of
the fill fluid must be calculated in reference to the
process fluid being measured
Glycerin (Specific Gravity=1.26) for the impulse tubes a
correction must be made.
DP span of 100”= physical height difference of impulse tubes
on vessel
SG of fluid being measured (Oil = 0.68)
Glycerin filled tubes (SG = 1.26)
Since the Low Pressure Leg will be filled with Glycerin we
multiply the span by the SG of the Fill Fluid
100” x 1.26 = 126” so the Lower Range value will be -126”
Span will be the LRV – (SG of fluid) x ( tank Level span) = 68”
-126” + 68” = -58”
-126 LRV
-58 URV
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
why we r opening HOT BYPASS valve during startup of a compressor?
What is the minimum rating availalbe for weld neck orifice in market?
please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com
If P will increase then what will happen with PID?
What are the type of bonnets in the control valves?
What is the difference between working pressure and calibration pressure of a control valve
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?
Can I calibrate the Electromagnetic Flow Meter on line and How.
What is loop1 and loop2 in MTS LT?
hello sir/madam, I,Subramanian need 5yrs placement papers of officer trainee of Instrumentation technology.pls send to this mail id mani_nxtgen@yahoo.co.in please do the needful. with regards, subramanian.v
what is the input of digital counter during the the calibration time?
send me model hpcl questions pleas..........my mail id mohideen.dharvesh@gmail.com
How to change dcs card in online. (Dsc is maxdna)
What is the constant voltage unit?
while i check zero check for dp flow transmitter some fluctuating came (0 to 458 kg/h) what is the reason?