How to take Vector group test of Transformer?
Answer Posted / prasad talada
1.1U1V1W-which is primary -Delta Connection
2.2U2V2W- Which is secondary-Star connection
3.join 1U& 2U terminals
4.Supply 1U-1V-1W 440v Measured
a.1U-1V
b.1V-1w
c.1W-1U
d.1W-2W
e.1V-2W
f.1V-2V
g.1W-2V
h.1U-2N
i.1V-2N
TO CHECK
1.1V-2W=1V-2V
2.1W-2V>1W-2W
3.1U-1V=1V-2N+1U-2N
From above check(1,2) the vector group of transformer is
verified
| Is This Answer Correct ? | 9 Yes | 3 No |
Post New Answer View All Answers
why capacitance effect is predominant in underground cable transmission and inductance effect is predominant in over head line transmission?
how is working bearing heater?
how to erect roof control panel?
why the arc welding machines require parallel earthing systems? ie why each machines are connected to earth pit by separate wires during earthing? wats it adavantages?
What kind of Neutral CT can be placed in 11/0.433KV transformer to be used and what are its specification?
what is the difference between megger and earth resister ??
Electrical 'C' license full abbreviation , and full form
what is KSR type transmission tower? What is LSR type transmission tower?
What is pi controller?
11KV AND 22KV NETWORK KW CAPACITY IN RING AND RADIAL?
How to calculate Voltage regulation of 22 KV Over head Line.
i have attended the interview on 4th June,08 at Kolkata in IOCL, can anybody tell me what is its result
how to check regenerative load in drived motor
How to Make relay co ordination chart for a Electrical power distribution of a plant
A 100 kVA , 400 v/250 kv testing transformer has 8% leakage reactance and resistance on 100 KVA base . A cable has to be tested at 500 kv using the above transformer as a resonant transformer at 50 hz . if the charging current of the cable at 500 kv is 0.4 A find the series inductance required . Assume 2% resistance for the inductor to be used and the connecting leads . Neglect dielectric loss of hte cable . what will be the input voltage to the transformer ?