what is the design voltage for 6.6KV 2000 KVAR HT capacitor?

Answer Posted / altaf

It is 7.2kV. This is arrived by taking into account 10%
increase in supply voltage & rounded off. However this is
for installation where series reactors are not used. In
case a reactor is used (6% for HT) then the design voltage
is 6.6x1.1/(1-6/100) = 7.72kV. The design kVAr also needs
to be increased accordingly otherwise the output is reduced
and detuning percentage changes & detuning frequency
deviates.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHAT WOULD BE THE FORMULA OF WIRE GAUGE FOR A FULL LOAD CURRENT

1682


ACB & VCB how do work and saftes and how can maintenance in this and parts name show with picture

1624


The specific heats of the gas at constant pressure and constant volume are respectively 1.0 kJ/kg K and 0.72 kJ/kg K; the value of R for the gas is

690


What happen if 200 KVAR capacitor connected to power continuesly?

1646


Explain thin film resistors and wire-wound resistors

631






Why the unit sizes of hydro generating machines are not standardized as in case of thermal powerplants?

606


What is dynamo function in DG sets and draw block diagram?

1577


ho can we calculate the conductor insulation value according to their ratings like voltage,current etc.how insulation value related with voltage,current and power of amachine

1571


can i use the six sigma method which is used in management area, in state estimation of power systems?

1370


which type of effect of turbine and generator reverse power protection ?

3748


how maney type tempereture measurement ?

1815


Can XLPE/SWB/PVC (P3) 7C X 2.5mm2 be replaced by Can XLPE/SWB/PVC (P2) 7C X 2.5mm2??? P3 vs P2

1348


The shot circuit in any winding of transformer result? Explain

784


what's the requirement of Dy11d0 connection of 3 phase transformer?what's use of it?

7370


what happen if the load connected to the induction motor is taken away? the same question for synchoronous generator in synch i think that the the exitation voltage will appear on the terminal only if so plz answer me

1525