I hv a question regarding power factor improvement just
after transformer. I request you to reply me plzz. thank
you sir.
My friend has a small unit of fabrication. in his factory
the main load is a welding machine, lathe machine, grinding
machine. this load is not continuous type. now our
electricity board has installed 16 KVA, 11000/433 V
transformer for our factory. In the energy meter (trivector
meter) at LV side of transformer, i hv seen power factor
value of 0.15 only when only 3 KW load was flowing. Further
electricity board has suggested to install 4 KVAR capacitor
at LV side after energy meter. Now my question is that if
we permanantly install and switch on 4 KVAR capacitor after
energy meter, during some load on transformer and also
without any load on transformer, wht will be the power
factor shown in energy meter?i dont want to get any penalty
by electricity board, so plz suggest me if i can
permanantly install and switch on the 4 kvar capacitor or
not at LV side of transformer just after energy meter?
Thank you again and awaiting for ur positive reply soon.
Answer Posted / raj
You have to calculate and put partially some capacitor
permanentely ON which will neutralized or improve the PF
when Transformer charged with NO load condition and other
capacitor should be connect through contactor so that as
welding machine will on capacitor will on ( interlocking
between both ).If PF increase or reached to Leading side
means it will work as a load and you have to pay extra
amount in your bill.
PF Calculation Formula
required capa.(kvar)=p*(tan(inv cos(pf1))- tan(inv cos(pf2))
p= total power in kw
pf1=actual pf
pf2=required pf
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?
what is difference between speed mode and torque mode in motor?? explain in simple words please.
what is booster? and how it is connected in a circuit?
Please tell me the earthing procedures adopted for the STAR-STAR 3 Phase transformer in india and give a better sugession for earthing
Is any generator is developed which is operated with out diesal or other expensive source?
how to set the time in digital timer ?
how to find out 3 phase complex power in per unit in unbalanced system?
Capacitor is load free component but why ampere meter shows current when capacitor bank breaker close?
how can i apilly for electrical c licencese.sir,i completed B.Tech in electrical & electronics engineering in 201onot working any company
hi, i have 3x200KVA and 2 x 80KVA UPS with battery bank of 150AH 68Nos. and 100AH 204Nos., i need to install AC either ductable or PAC type, so can you help me to calculate heat load and capacity of the AC to install.
in a simple IDMT relay we use neutral point of ct for earth fault then what is the requirement of neutral ct and cbct?
How stabilizer works??
explain the mode of metal iranafer in Co,welding
which type of effect of turbine and generator reverse power protection ?
if any body have question paper of railway (section engineering),then plz send me .i will thank of him/her.