can i know how to design overcurrent setting and earth
fault for 11kv & o.433kv system assuming tx 1000kva.
Answer Posted / prakash.
First selected for ct ratio in HT panel.1000kva transformer full load current in primary 52.5amps.so ct ratio in 60amps(60/5).
Now relay setting for over current 55amps.
And earth fault setting 0.5amps in ct secondary amps..
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
dear sir/madam i want to get some knowledge about RRB EXAMINATION(section engineer) 1- what is minimum cut off 2- wht portion is major portion . 3- can any body provide Sample paper. thanks & regards ashish
what are the 4 rules to start the motor?
For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?
Why AC & DC capacitor are use in UPS ??????????????????
what is a synchronizing lamp ?
What is stepper motor?
What is tan delta & PPM in transformer? and whats its IS value?
How to calculate flow of water delivered by pump when pressure & size of pipe line is given
role of europe union in UK safety legistlation (electrical safety)
Give atleast 20 alternating current apparatus and devices.
how to modify DOL control panel into Delta Y connection?
What is the function of probe in cro?
what is the function of choke in the flourcent tube lights and why the colour is in white mostly in flourcent tube lights
when we have to purchase the transformer by own i.e how much load will preferred HT connection?
Actually I have a doubt on neutral and earth.we use Ac power without taking neutral by connecting to earth,but at that time does it affects on efficiency of any electrical components or no? If yes how?