Sir if i have 2kv ups in which 17ah 8 battries load 600watts
how much back up time i get and if i put 6kv ups with the
same no of battries same amp can i get more back up time
please give reply exactly what is the procedure to calculate
back up time for different kv,s
Answer Posted / k.prakashchandra
The KVA of UPS has nothing to do with back up time . The
back up time is = stored energy in watt hour/load in watt.In
this case Back up time = 17 x 8 x 12 (voltage of each
battery)/ 600 =2.72 hour
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What size cable (based on voltage drop) is required to supply a 40 A three phase boiler if the wiring system is 75V single insulated cables installed in non-metallic rigid conduit 56m from the main switchboard? Voltage drop in the consumer's mains is 8V.
Explain what is electric traction? Explain few advantages of electric traction system?
what is PWM in IGBT and how it works for drive.?
Why compensation is necessary in feedback control system?
State thevenintheorem?
Advantage of LT panel vs HT panel
How can I known multiplying factor .without multiplying table
which mm cable should be used for 1.hp immersible pump motor for the distance of 330 metres?
WE ARE PLACE A NEW 75 KW MOTOR FOR JPF.IT IS CONNECTED IN M.C.C. WHEN WE ARE STARTING M.C.C.INCOMER IS TRIPPED.THEN WE ARE CONNECTED IN P.C.C WITH A MM30 RELAY PROTECTION THEN WE ARE STARTED MOTOR WILL RUN SMOOTHLY.
i have to install a HT panel, what components, I have to use in this and what will the diagram of that diagram,please tell me each and everything.
Why can't we parallel the secondary circuits of two voltage transformers?
Explain forward resistance, static resistance and dynamic resistance of a pn junction diode.
what is LSR?
What Is HO factor in power selection
Why are the cores of large transformers built up of circular transactions ?