Answer Posted / sudhanva madhukar mahamuni
Hello To every One,
This is Sudhanva Madhukar Mahamuni Electrical Design
Engineer. The reason behind the same is not a alternator /
generator. The reason behind the same is diesel engine.
(Surprise!!!!!!!!!!)
Carefully read the catalog of DG Set for e.g. for 750kVA its
written as 750kVA / 600kW @ 0.8 pf. It means that alternator
size is 750kVA and 600kW is of Diesel engine. It means that
diesel engine can delivery only 600kW power. so if we like
to maintain the same then we need to keep 750kVA load on DG
@ 0.8 (750 x 0.8 = 600kW.
But assume that your load on alternator is 600kVA then you
are allow to improve your power factor till unity i.e. 1.
Therefore load on engine will be 600kVA x 1 = 600kW.
Summary : if multiplication of electrical load (in kVA) to
Power Factor will be upto or less than kW rating of diesel
engine then we can play with power factor i.e. lead or lag.
Note : If we will not do as above mentioned and improve the
power factor then engine will cease off (dead) i.e. cant
repair or modify.
For further clarification you can call me or mail me on
sudhanvamahamuni@structwel.com or sudhanvamahamuni@gmail.com
Regards
Mahamuni
9769317386
Is This Answer Correct ? | 8 Yes | 1 No |
Post New Answer View All Answers
can anyone provide me a amf panel control wiring using ec-2 relay?
is ac supply can store
why in the three pin plug all 3 pins are cutted ?
how will calculate the safe starting current of 3-phase squirrel cage induction motor?
What is the equivalent circuit of a transformer and its vector diagram?
what is the reqirred voltage in HT motor to get full RPM on no load test?
A parallel flow heat exchanger will perform better than a counter flow heat exchanger. State if the statement is true or false.
how many types are their in switchyard or substation(like D,I TYPE), what is differant between them
i am studying in final year can i allowed for 23rd UES of Indian army
How much load can be taken for chiller from 1500 kva transformer
how to select automotive wire by mathematical equation with given current, vlotage and resistance
why most of junction box vendors providing T5/T6 Temp class jb's for T3 area any special reason?
What is PQA???Applications........
How grounding is different than earthings?
Single line diagrams for star to delta and DOL starters.