Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the significance of 3.5 core cable? or what does this
half core mean and why is it required?

Answer Posted / bharani

3.5 core in an armoured cable means, neutral cable will be
half in diameter that of phase cable .This is used in LT
circuit where you may use 3 phase load as well as single
phase load.If the load on three phases is balanced, the
neutral current will be less hence half core for neutral may
be sufficient. But if the load on three phases tends to vary
a lot, then neutral curent may increase and in such cases 4
core cable instead of 3.5 core would be recommended.

Is This Answer Correct ?    5 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to find 5 kilo meter long under ground 33 kv cable fault location if IR VALUE shows 0.05 M ohm @5000 volt.and cable fault locator shows some time fault distance 3 kilo meter ,3.7 kilo meter and some time 1 kilo meter? now how to find the fault location that where is leakage. note--it is tested with 5000 kv megger and insulation resistance is 0.05 M ohm. and some time 0.03 M ohm comes.

2194


What is float cum boost charging system?

2041


I want to replace the 3 KW DC motor with AC motor so what should be the rating of AC motor? Details Of DC motor to be changed with AC are - Kw - 3, Vf - 310, If - 0.15, Va - 400, Ia - 13, RPM - 2400

1805


hi i have applied for lic of india south cenrtal zonal ,hyd. i didnt get hall ticket till now.let me know how can i get form internet

1980


What are the different sign conventions used in electric circuits?

1151


What willbe change in programming when we use 5/3 solenoid inplace of 5/2 in operating of a cylinder?

2045


what is the transmission loss for electrical supply? specifically a large shopping complex where the grid is half KM away, what will the % of transmission loss? is there any transmission loss for captive unit generation for above set? thanks

1954


What are the advantages of instrument transformer?

1139


What are the causes of having an rmu explode after installation? And how do u treat the bushings of an rmu?

2484


If I have Energy Meter Ratio as 100:5 & Also I have CT Ratio as 50:5 then what will be my multiplying Factor(M.F.)

1952


Can you any one explain application of buccholz relay operation and pressure relif device operation of power transformer

1839


one electromagnet is called

1897


1.what is mean by 8/20 micro sec waveshape

2203


please send me RRB electrical engineer previous year questions for Sr. Section Engineer

1923


why transformer tank is in rectangular shape what happen when it is in step shape

1436