When we change the tap position of 10MVA transformer it
suddenly tripped with Out of step indication and also with
Static differential relay indication, Transformer Bucholz
relay indn and Low oil level indication. Before 1 week the
same problem occured by changing the tap position. but at
that time only oltc bucholz relay activated. After testing
the TxR Relay team & PET team cant find any solid reason.
The values are ok also. So plz answer wat's the reason for
this incident? anybody plz help.
Answer Posted / k.prakashchandra
OLTC has contact switches on rotating spindle and diverter
switch. Bucholtz relay acts as the oil is burnt in the
chamber due to arcing caused by loose contact .The spring
tension of the switches are to be checked for correct
tightness.If the contact is not correct ,the differential
relay may also act due to imbalance of currents.Do not
operate OLTC till the fault is set right.And the oil may
have to reconditioned.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Do closed loop systems require manual input?
What is the formula to calculate a three phase alternator
How 3 phase invertor works?
how to estimate wiring ins roughing ins. and boxes
Define conversion efficiency of a power amplifier.
WHAT DO YOU MEAN THE DIFFERENT TYPE OF CURVES OF RELAY LIKE STANDARD INVERSE, VARY INVERSE, NORMAL INVERSE, LONG INVERSE ETC....
What is the suitable transmission voltage?
How one can check the MAIN of a house wiring ?
Why do we apply both Differential and REF (HV and LV) protection schemes on YNyn configuration of a transformer?
What is electrical grounding?
what is apparent poewr, reactive power, & active power?
direction of tarbine& genrator
HOW TO SET THE EARTH FAULT SETTINGS IN ACB????????????
What are the advantages of nichols chart?
How to apply 'c' license and also explain what is difference between 'c' and 'b'license.i am also working in one of the private company.i have finished my diploma in 2014 .i have already finished in ITI electrician course.....