if 1hp jet motar drop voltage when start from 220v to 120v give the reason and solution.
Answer Posted / k.prakashchandra
It may be due to voltage drop in the line.Momentary drop
while starting only, can be ignored.Connect a load of about
500W and check for voltage drop.If the drop persists then
examine for loose connection/joint which could be any where
from dist transformer to the point of measurement .If you
don't detect any fault still, test the motor.Voltage between
neutral and the earth indicates a loose joint in the neutral.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
If more than rated DC voltage appears across trip coil of the breaker, what will happen? e.g. in 110V DC circuit system, if voltage across battery terminal showing 121 V
upto how many load can v connect to stabilizer which is used for tv
Give two basic speed control scheme of dc shunt motor?
what is the ATS .And how it works.
what are problems caused by the pdu in rack server
Why in ESP Positive earthed
What is K-rated transformer? What is the use of it? What can be the size(pls provide calculation if possible) of K- factor transformer for 550kW,690V motor operating with drive (VFD)?
Is there any rule to select the voltage of motor based on KW rating? What is the rating above which lt motor becomes the HT motor?.
how to measure earth resistance of a substation
3ph motor running with unequal kw and different pf what are the reasons
Earth leakage relay basic knowledge principle
A 15 kw squirrel cage motor having a maximum efficiency of 90% on a continuous full load has temperature rise of 42 degrees celcius after 30 min and 52 degrees celcius after 1 hr under the above operation conditions. a) calculate its final steady state temperature rise on continuous load and the heating time constatnt. b) if the motor is operated on a short load for 9 min estimate its temperature rise. c) calculate the maximum overload that can be applied on a short, 9 min rating so that the temperature rise is the same as the final steady state temperature rise on continuous load.
what is the difference between an alternator and a synchronous motor
WE HAVE THE DC RECTIFIER 1500A, INPUT VOLTAGE IS 3 PHASE. HOW TO CALICULATE THE LOAD? 3 PHASE SIDE EITHER dC SIDE. PLEASE SUGGEST ME
what is W.T?specify the acceptable range?