Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

my company total load is 1000kw, 415volt, all load are
inductive load. incoming powerfactor is .8. we want to
have0.95 pf connecting capacitors. so now how much rating of
capacitors we have to connect? show how?

Answer Posted / rsundareee

your original p.f is 0.8(Tan 0.8) and you required p.f is
0.95(Tan 0.95).Required p.f = kW(Tan0.8 - Tan 0.95),when
you select the breaker rating of Capacitor bank you have to
conside the Hormonics (33%),For exambe breaker rating will
be 100A it shall be (100+33=133) 160A MCCB.

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why 15Amp. MCB is suitable to carry load of 1.5Ton Ac please Explain?

2223


How to do stting of vl250 siemens MCCB

3004


What is the tension required for the 25000 CFM AHU belt

2533


specify the inbuilt protections in DG

2118


In power transmission using open belts or horizontal shafts it is preferable to have the slack side of the belt on the top because

1282


i have to install a HT panel, what components, I have to use in this and what will the diagram of that diagram,please tell me each and everything.

1849


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1966


how to determine motor size for a fan application?

2351


i need of the bhel question papers along with answers and also give some website names for the downloading question (electrical and electronics engg question)please help me....

1976


How to calculate the current of Highpressure Mercury Vapour Lamp?what is the basis?whether we have to consider power factor or not?

2226


How to calculate the value of earth capacitance in a transmission line.

2414


What is capacitance?

1305


What is the mmf,rgt and ngt please brief completely

1690


234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,

2093


why the making current is more than then the breaking current and if its true then its about a controling circuit or breaker power contact points

2112