How to select a D.G set for calculated load of 110kW..?
Answer Posted / mahesh sali
FOR 110 KW , SAY AT 0.8 PF.
WE KNOW THAT
KVA = KW/PF
KVA=110/0.8
KVA = 137.5 KVA
ASSUME THAT ABOVE LOAD IS MOTOR
FOR
AS PER NEC SAY THAT
25% EXTRA AS PER NORMS,
I=KVA/1.732*V ASSUME:- V-415 V
I=191.29 AMPS.
THEREFORE,
I = 1.25 * 191.29
I= 240 AMPS.
KVA= 1.732 *240*415
KVA=173 KVA , DEMAND LOAD
AS PER RULE
80% LOADING ON DG SET
KVA=173/0.8
KVA=216 KVA DG SET RATING
AS PER STD.RANGE OF DG SET -725 KVA AT 0.8 PF , 415 V
216
| Is This Answer Correct ? | 16 Yes | 8 No |
Post New Answer View All Answers
In AC if the direction of current keeps reversing every half cycle, how does it propogate through the transmission lines?
what is earth fault relay 64T, why it is used in main Incomer and neutral CT of Transformer.
If one lamp connects between two phases it will glow or not?
What is the safety of UPS?
WHERE NEUTRAL WIRE IS CONNECTED AT DOMESTIC TO TRANSMISSION LINE(SINGLE PHASE TO THREE PHASE)
what is dry and wet frequency withstand voltage? why & where it is used??
What happen when change order of CT in GIS feeder?
what are the different sizes of U.G. cable & where these cabl;es are used according to voltage ..
what are the ''pitting rings''and how cn they be controlled in a series generator
Apparent power is expressed as V * I(Conjugate). Why not in V * I ?
Dear All we are having a problem in G120 BOP showing alarm A0503, F0052, F0060 we can not remove fault alarm ,Please any body help us. kowsar
how is the cable tray designed & how its total length is calculated for an Industrial plant Say for Ex. (500KW Motor Load)
when we have to use UPF wattmeter and LPF wattmeter? what is the difference between UPF and LPF wattmeter in terms of construction?
What is the difference between a fuse and a breaker?
What is inrush current?