My requirement is 1VA,50/5A Current Transformer for
Metering .If I select 15VA , 50/5A CT.Is there any
possibility of Technical Problem ?

Answer Posted / roy

Hi ,
Yes there is . and a highr rated VA is never recommented
for metering ( again it depends the accuracy but still not
used as per IEC)
Note:The accuracy class will not be guaranteed for burdens
above rated burden or below 25% of the rated burden.Check
IEC 60044
Amd more interstingly , we are allowing or excepting to
saturate this metering core during fault to protect the
metering Equipment reff. IEC 44

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are the difference between CT/PT operated Meter and RRAMR Meter for HT/LT application?

2014


what is a types of short circuit and what is a types of distance protection tests

1765


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1971


i am venkat i got gre 930(verbal 270 quanta 660) and my toefl score 105..here question is why u got less score in gre ? what i supposed to tell...any chance of rejection is there...my accadamics record is very good

1725


What are m circles?

659






In siemens S7-300 PLC, what is function and function block ? What is the difference between them ? When to use function and when to use function block ?

1641


what is the earth current,reverse power,electrical trip generator short circuit,low voltage, high voltage please discribe me

1641


what is Anti-pumping?

1498


what sort of general awareness questions are asked in o.n.g.c entrance exam?????????????????

4208


Name the test signals used in control system

792


Explain about p.t?

665


why dc is used in control circuit for mv & hv switchgear instead of ac

1453


CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS

1408


Explain the difference between verilog task and verilog function?

751


Proviiding the Dedicated N earth and individual Body Earths ,Finally these all looped /Now my Question :- will it not harm in case of Transformer Fault current flows in Dediacted N Earthing to Looped Body Earthing.

1743