My requirement is 1VA,50/5A Current Transformer for
Metering .If I select 15VA , 50/5A CT.Is there any
possibility of Technical Problem ?
Answer Posted / roy
Hi ,
Yes there is . and a highr rated VA is never recommented
for metering ( again it depends the accuracy but still not
used as per IEC)
Note:The accuracy class will not be guaranteed for burdens
above rated burden or below 25% of the rated burden.Check
IEC 60044
Amd more interstingly , we are allowing or excepting to
saturate this metering core during fault to protect the
metering Equipment reff. IEC 44
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What are the difference between CT/PT operated Meter and RRAMR Meter for HT/LT application?
what is a types of short circuit and what is a types of distance protection tests
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
i am venkat i got gre 930(verbal 270 quanta 660) and my toefl score 105..here question is why u got less score in gre ? what i supposed to tell...any chance of rejection is there...my accadamics record is very good
What are m circles?
In siemens S7-300 PLC, what is function and function block ? What is the difference between them ? When to use function and when to use function block ?
what is the earth current,reverse power,electrical trip generator short circuit,low voltage, high voltage please discribe me
what is Anti-pumping?
what sort of general awareness questions are asked in o.n.g.c entrance exam?????????????????
Name the test signals used in control system
Explain about p.t?
why dc is used in control circuit for mv & hv switchgear instead of ac
CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS
Explain the difference between verilog task and verilog function?
Proviiding the Dedicated N earth and individual Body Earths ,Finally these all looped /Now my Question :- will it not harm in case of Transformer Fault current flows in Dediacted N Earthing to Looped Body Earthing.