My requirement is 1VA,50/5A Current Transformer for
Metering .If I select 15VA , 50/5A CT.Is there any
possibility of Technical Problem ?
Answer Posted / roy
Hi ,
Yes there is . and a highr rated VA is never recommented
for metering ( again it depends the accuracy but still not
used as per IEC)
Note:The accuracy class will not be guaranteed for burdens
above rated burden or below 25% of the rated burden.Check
IEC 60044
Amd more interstingly , we are allowing or excepting to
saturate this metering core during fault to protect the
metering Equipment reff. IEC 44
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What is mathematical model of a control system?
What is meant by a stray loss of a induction motor??? What is the equation to find it
What we mean by vintage of an engine+Generator?
defination of lines
Can you used moeller lzm1 mccb in a dc system with 125vdc and 20ka short circuit current , beside is it have 24 or 48 volt shunt ? Beside how long current can through from An MCB shunt contacts? (like Z7-AS 24 V)?
If symmetrical fault occurs at the terminal of a synchronous motor then how the motor will act...explain it..
A jet of fluid strikes a plate What was the force required to counter it?
how ct burden,magnetising current,ratio and knee point voltage are related & derived
How to select a contactor? How many types of contactors are available
In Dyn11 power transformer if any one of the 3 phases connected to earth in star connected side then please explain effect of the current flow in delta connected side of transformer.(In this case if one phase is shorted to ground in star connected side then we observe the current flow in two phases only not three phases in delta connected primary side. Please explain why it is so?)
What Maximam Gap Taibaar & Bush
Hello Guys !! i want to rrb section engineer electrical(signal) previous model papers? any body help me?
does any one know where we can purchase insulation oil for high voltage oil filled cables
specific difference of ICT&Auto Transformer
how do we calculate length of starting time and repeated starting of a direct online starter?