If we give 2334 A, 540V on Primary side of 1.125 MVA step up
transformer, then what will be the Secondary Current, If
Secondary Voltage=11 KV?
Answer Posted / ramendra shukla
As we know the Voltage & current relation for transformer-
V1/V2 = I2/I1
We Know,
VI= 540 V ; V2= 11KV or 11000 V; & I1= 2334 Amps.
By putting thease value on Relation-
540/11000= I2/2334
So,
I2 = 114.5 Amps
| Is This Answer Correct ? | 30 Yes | 4 No |
Post New Answer View All Answers
In convertor can we use rectifier thyristor in place of invertor thyristor with explain.
According to IEC60034-14, When the vibration monitoring system required for motor Bearing. above which KW, it is required? and for what type of bearing the vibration probe is provided.
can i connect the two phases of scott connected transformer,if not why?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
one electromagnet is called
Can I use distributon class/transmission class Lightning arresots for protecting the building? If not why please explain?
Merits & Demarits of Oil circuit & Air circuit breakers ?
what is the difference between electrical choke and electronic choke?
In synchronization circuit what is the function of Interposing voltage transformer(IVT)and Reverse voltage transformer(RVT)
What are the different methodes for calculating the short circuit Current?
at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)
1 hp is equal to how much watt?
IN 1000kva transformer where the oil and winding temperature sensors is connected
In three pin plug 6 amp. 220V ac rating. Why earth pin diameter is higher than other two pin? What its purpose ?
Comment on the working principle of operation of a single-phase transformer.