in 3 phase (4 wire) star connection - is current pass through
neutral??

Answer Posted / ankush miglani 9718037333, eba

for star connections if the load is balanced, the phasor
sum of the three currents is zero.
but if the load is unbalanced, the all three phases do not
carry the same load or if there is any fault, a current
passes thru the neutral and the amount is equal to the
current that balances the all three phase currents.

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how we can do the insulation on secondary of ct explain and so that tan delta will within limit

1448


boiler is running in rankine cycle and deisel generator is....?

1565


What is the tension required for the 25000 CFM AHU belt

2051


What is the drawback of class b amplifier? How is this minimized?

668


how to control dc motor?

1416






how to remover corona effect and hysteresis losses from contactor

1562


Whar is the KvA rating of 33Kv substation & actual kv rating of power generaating station.

1880


Rules and standards of electrical control wiring ?

635


what are the breakdown voltage rating of mini- curcuit'transfarmer!

1659


what is transient stability analysis means?

1666


two way ckt diagram can be drawn by how many ways? give diagram

1337


apti mainly on logical reasoning, verbal and non-verbal ability (70 percent) and remaining technical. I was in ee but technical had mech ques like on turbines and welding.

1723


How can we calculate the motor frame sizes?

2912


Why frame of the motor is specified?. If we mention KW and voltage level,automatically frame is decided or separately frame is compulsory to mention?.

1293


What is s-domain and its significance?

728