why is it that the HT motors & motors having very low kW
rating(<1kW) have windings connected in STAR, whereas the
motors having in between kW ratings have DELTA connected
windings??
Answer Posted / avdhesh
The basic differance in star and delta connection is that
in delta connection voltage across the winding is line
voltage (V-line) and in star connection it is phase voltage
(V-line/1.73). Same way current in each winding in delta
connection will be (I-line/1.73) and in star connection it
will be line current(I-line). Now to design any motor one
has to take cost of insulation as well as copper.In delta
connection you need higher insulation and in star
connection you need thick conductor to cary high current.
For HT motors current is less as voltage applied is high
hence to reduce insulation cost star connection is made.
For higher rating LT motors since current is high delta
configuration is recommonded.
If we do not follow above than cost and size of machine
willbe increase.
Hope this is the answer of your question.
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
design a 3 bit synchronous and asynchronous counter using T- flipflop
what does mean of RCT and STR in diffrential CT?
What is the difference between Static and servo controlled voltage stablizer?
what is stper motor
what is the relationship between phase & neutral
in ring main system we use the isolater b/w transfer bus and main bus if we r not use isolatar than wat will be the effect in our sys.
What are diffrent type of road taxes?
Dears we deal in Chemical are Plate earthing. Kindly call if any requirement and questions. Tech Earth Solutions Mohit Verma 8791071007
what is the difference b/w absolute encoder and incremental encoder?
In EB metering we face problem kva jump even in no load condition.can any one help to control this
Why phase sequence must be same in any ht motor or generator circuit?if phase sequence doesn't same whatever will be affect on circuit?
How to Design green buildings services? What is the advantage to design green building?
What about electrical Units. discrive in detail
for 5KW resistive load can anyone please suggest me whether to go for UPS/Inverter or Generator depending upon cost calulations
How to calculate loses in transformer of 160 KVA ?