In your own words, would you expect an ultrasonic level
device to work better in a pressure vessel with a high
pressure or a strong vacuum, and why?
Answer Posted / pavan wagh
At high pressure in pressurized vessel ultrasonic signal gets suppressed substantially ,same is the case with strong vacuum where medium (air) of signal transfer is absent.
In both cases DP transmitter is the best choice for good accuracy. For level measurement with DP transmitter density compensation is essential,as liquid (water) density changes at high pressure and high temperature.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Which type of pressure can be measured by these elements?
Actual using of tube bender to bend 2 opposite 90 deg at correct measurement center to center of tubing.
When doing a liquid seal on a differential flow transmitter , most of the time the sealing liquid will be heavier then the process fluid. For wich application will the sealing liquid be lighter than the process fluid if transmitter is mounted below the process line.
what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .
Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75
The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is:
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. STN0149
---- ERROR = 2 WARNING = 1 ----
Background:
>Updated the ExaOPC software on the STN from 3.60 to 3.75
>STN operating system is Windows Server 2008 R2
>HIS operating system is Windows Server 2016 Stanard
Solutions attempted include:
>Ensuring all IP addresses are correct and all networked devices can be pinged.
>The ability to ping a device using its host name from another device (
Calibration procedure for electro magnetic flow meter
why using negative supply for bentley nevada vibration system ?
How to Calibrate Ultrasonic flow Transmitter in Field
Dear Friends, we are planning to design Power distribution and Fiber optic in the same cabinet.Like Front side Fiber optic and Rear side Power distribution.Is it any possibility of problem occurs like interference etc? Your answer is highly appreciate.
Explain why plc require in analog input 4-20amp & 0-10 volt?
In dcs panel we are using diff type of modules ?what is module ? what is the use of modules ?diff type of module?
I want to know the questions asked in ONGC interview(after being selected in the written exam) for Instrumentation branch.Kindly help.
what would be the minimum flow rate that we can measure on rotameter..?
What is Droop? What is Step/Gradient Limiter in Turbine Governor control?
What is rang ability?